PVI 13KW and PVI 15KW INVERTERS
A breakthrough in price and quality
OVERVIEW: INTEGRATED PV INVERTER
The Solectria Renewables PVI 13KW and PVI 15KW are rugged, DSP-controlled PV inverters for grid connected commercial, industrial and utility 3-fase PV systems. The core of the inverter, Solectria Renewables' proven DMGI 245 distributed generation inverter, uses state of the art contrl techniques and devices including space vector PWM, a precision MPT algorithm, and low-loss rench-gate IGBTs.
With inverter power electronics efficiency up to 97% (95.8% including the transformer) and fully integrated packaging, the PVI 13KW and PVI 15KW set a new industry standard for efficiency, ease of installation, and reliability.
APPLICATIONS
- 10-15kW, 60Hz, 208, 240 or 480VAC, 3-phase, grid-tied commercial PV systems (up to 15-18kW DC-STC).
- Multiple inverters can be used together for 20-30kW, 30-45kW, 40-60kW (AC) or larger PV systems. Ideal for 30-35kW, 36-54kW, 48-72kW DC STC arrays.
- Designed for mounting as desired, indoor/outdoor, driving rain and drifting snow: rooftop/ground/wall.
- Versions for other renewable and distributed generation applications available.
FEATURES
- Fully integrated design includes transformer, filters, AC & DC disconnects, DC combiner-fuses.
- Premium overall efficiency.
- Simple set-up and connections (connect DC from PV strings and 3-phase AC connections).
- Precision DSP-controlled Maximum power tracking Algorithm.
- High-reliability design, based on 20 years of power electronics products, includes sealed power and signal control electronics, high-efficiency magnetics.
- No night-time standby losses.
- Optional 6-7 fuse PV combiner in DC disconnect.
- Optional "Blizzard-Proof", gasketed disconnects, recommended for rooftop or other severe locations.
- Optional forward facing disconnects option (version).
- Optional positive grounding version
CONNECTIVITY
- RS232 port and software for diagnostics and data capture with PC.
- RS485 port for communication with multiple inverters in larger system and long communication lines.
- SolrenView or Fat Spaniel Inverter-Direct Internet, and/or revenue-grade monitoring options available. Also compatible with Energy Recommerce, Darker and others.
SAFETY FEATURES
- Electronic temperature protection, intelligent cooling
- DC ground-fault detection and interrupt.
- Current and voltage limit protections.
- Standards-compliance: Listed to UL 1741 (IEEE Std 1547) and tested to NY SIR Surge Test Requirements (IEEE 62.41). Listed on CEC's eligible equipment list.
|
PVI 13KW
|
PVI 15KW
|
OUTPUT
|
| Maximum Cont. Power |
13.2 kW AC
|
15 kW AC |
| Power Factor |
Unity |
| Voltage (L-L), -12%, +10% |
208/240/4080 VAC, 3-Ph |
| Maximum Cont, Current (AC) |
37/32/16 A |
42/36/18 A |
| Current Distortion |
< 5% THD, Nom Power |
| Frequency, ±1% |
60 Hz |
| Inverter peak Efficiency(1) |
95.8% |
95.8% |
INPUT
|
| Array Configuration |
Monopole, negative grounded (pos gnd opt) |
Max Voc(2)
|
475 VDC |
Maximum DC Current
|
60 A |
68 A
|
|
MPT Voltage Range
CEC Full Power Voltage Range
|
225-380 VDC
235-380 VDC
|
PROTECTION (3)
|
|
AC Grid-Connection (Standards Compliance: See "Safety Features")
|
Over/Under Voltage Over Current Over/Under Freq. |
AC Disconnect (Integral)
|
NEMA 3R, w/fuses |
DC Combiner-Fuse Enclosure (Optional (4))
|
10A/15A fuses available, 6-7 pole, NEMA3R, TVSS |
DC Disconnect (Integral)
|
Break load rated, NEMA 3R |
ENVIRONMENTAL
|
Ambient Temperature
|
-25 to 50 deg C |
Cooling
|
Forced Convection |
Enclosure
|
NEMA 3R |
Enclosure-electronics
|
Sealed, IP-62 |
GENERAL
|
Weight
|
376 lb(1) (171 kg) |
398 lb(1) (181 kg) |
Dimensions(5) (inches [mm])
|
34.5[876] · 26[660] · 13.6[345]
|
Warranty
|
5 years (10 & 15 extended available) |
Communications, Optional Data Acquisition
|
RS232, RS485, optional Solren View or Fat Spaniel, also compatible with others |
|
(1) Fully Integrated Package: Includes transformer, filters, fan, AC & DC disconnects, and combiner-fuse box (2) Max Open circuit voltage (Voc) of PV array=1.25 x Voc-rated (per NEC 690-7 ) (3) Complies with grid connection and safety standards ("Safety Features") (4) Integrated into inverter package if selected (5) Forward-facing disconnect option width is 47" (1194 mm)
|
DIMENSIONS

SYSTEM BLOCK DIAGRAM

|